Chiller-less Goal Line in 2026
Pumps, MCA, and 238 GPM/motor flow are locked identically across both generations ‚Äî only the required HX area and achievable approach change, because the two NVIDIA loop specs impose different capacity-rate balances on the same hardware. Every number below passes the Qmax = Cmin×(Thi−Tci) energy-balance check before being displayed.
Rack Reallocation GB200, 132kW/rack
Ground Zero Legacy CDU, real spec
| Basis | Capacity | Approach | Real power (2 motors) | MCA |
|---|---|---|---|---|
| Legacy CDU (ground zero) | 1.2 MW | 5.0K | 42.0 kW (at 120% field load) | 63A |
| Cool-E (both generations) | 2.0 MW | 2.4K / 7.0K | 18.0 / 18.5 kW | 27 / 37A |
Cool-E Spec locked pumps
How This Works
| Step | Logic | Result |
|---|---|---|
| 1. Facility flow vs. IT need | Q = flow × ΔT on both sides. GB200's wide 20K spread means the IT side needs less flow than the facility side already provides at 476 GPM | Cr = 0.827 — facility side has slack |
| 2. Spend the slack on area, not current | Growing the HX (not the pump) closes the gap to a tight approach | 93.0 m² HX → 2.4K approach |
| 3. Current follows flow only | MCA is a function of pump duty (238 GPM/motor), not HX size | 27A — unrelated to the 2.4K approach achieved |
| Why this beats a flow-scaling competitor | OCP's real 157A pays for a much bigger circuit to hit the same 3°C approach, because their lever is flow, not area | 83% less current, same generation |
Competitor Comparison real spec
Scaling, 2MW to 24MW 1-12 CDUs
Chiller/climate analysis (ASHRAE zone check, annual bin-hour model, Legacy-vs-Modern comparison) removed from this view — confirmed no impact between Cool-E and OCP anywhere tested, so it no longer earns space alongside the panels above that show the real differentiator. Underlying methodology and data are retained in this file's source for reuse if a specific climate or legacy-IT-hardware question comes up again.